Customization: | Available |
---|---|
Output Type: | Single |
Warranty: | 2 Years |
Still deciding? Get samples of US$ 6.2/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
MODEL:HDR-30 Single Output Industrial DIN Rail Power Supply
|
|||||||
|
|||||||
MODEL |
HDR-30-5 |
HDR-30-12 |
HDR-30-15 |
HDR-30-24 |
|||
OUTPUT |
DC Voltage |
5V |
12V |
15V |
24V |
||
Voltage Tolerance |
±2% |
±1% |
±1% |
±1% |
|||
Rated Current |
3A |
2A |
2A |
1.5A |
|||
Current Range |
0-3A |
0-2A |
0-2A |
0-1.5A |
|||
Rated Power |
15W |
24W |
30W |
36W |
|||
Ripple & Noise |
80mVp-p |
120mVp-p |
120mVp-p |
150mVp-p |
|||
DC Adjustment Range |
-5%,+10% |
±10% |
±10% |
±10% |
|||
Setup, Rise, Hold Time |
100ms,30ms/230VAC100ms,30ms/115VAC at full load |
||||||
INPUT |
Voltage Range |
85~264 VAC47~63 Hz; 120~370VDC |
|||||
AC Current |
0.88 A/115 V 0.48A/ 230 V |
||||||
Efficiency |
74% |
81% |
82% |
83% |
|||
Inrush Current |
Cold start 15A/115V 30A/230V |
||||||
PROTECTION |
Over Load |
105%~160% |
|||||
Protection type: Constant current limiting, recovers automatically after fault condition is removed |
|||||||
Over Voltage |
115%~135% |
||||||
Protection type: Shut down o/p voltage, re-power on to recover |
|||||||
ENVIRONMENT |
Working Temp., Humidity |
-20ºC~+60ºC;20%~90 %RH |
|||||
Storage Temp., Humidity |
-40ºC~+85ºC;10%~95 %RH |
||||||
Vibration |
10~500Hz,2G 10min/1cycle, period for 60min, each along X, Y, Z axes |
||||||
SAFETY |
Withstand Voltage |
I/P-O/P:3KVAC |
|||||
Isolation Resistance |
I/P-O/P:100M Ohms / 500VDC |
||||||
STANDARD |
Safety Standard |
Design refer to UL60950-1,TUV EN60950-1,EN50178 |
|||||
EMC Standard |
Design refer to EN55011,EN55022,EN61000-3-2,-3,EN61000-4-2,3,4,5,6,8,11,ENV50204,EN55024,EN61000-6-2,EN61204-3 |
||||||
OTHERS |
Weight |
0.27Kg |
|||||
Packing |
48pcs/14Kg/1.02CUFT |
||||||
NOTE |
1.All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25ºC of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″twisted pair-wire terminated with a 0.1μ & 47μ parallel capacitor. 3.Tolerance: includes set up tolerance, line regulation and load regulation. 4.The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. |